Combination Fire / Smoke Damper
Class I • 250°F or 350°F • 1½ Hour • Galvanized Steel • Airfoil Blade
STANDARD CONSTRUCTION
Frame
Frame Type
Blade
Blade Type
Axle materials
Axle Bearings
Linkage
Blade Seal
Jamb Seal
Closure Device
Closure Temp.
: 16-GA galvanized steel
: 5½" X ⅞" Galvanized steel Hat Channel
: 20-GA Double skin ( equivalent to 14-GA )
: Airfoil type
: Plated Solid Steel stub
: Oil impregnated bronze
: Plated steel angle & crank plates with stainless steel
pivots; In-jamb type
: Silicone
: Stainless steel
: Electric heat responsive device
: 165º F (73ºC)
OPTIONS
-
Exact Size (no undercut)
-
Actuators - 230V, 24V, 120V or Pneumatic
-
Right Hand and/or Internal Actuator Mounting Locations (Restrictions Apply)
-
Dual Position Indication (DPI) Switches
-
Sensotherm Re-Openable Heat Response Device (ESOT) for Electric Actuator
-
Sensotherm Re-Openable Heat Response Device (PSOT) for Pneumatic Actuator
-
Model SM-501 Flow-Rated Smoke Detector
-
Model 2151 No-Flow Smoke Detector (12” Minimum Damper Height)
-
Momentary Test Switch
-
Remote Test Box
-
Transformers
-
Tab-Lock Retaining Angles
-
Stainless Steel Bearings
-
Stainless Steel Axles
-
Security Bars
-
Copper Tubing (for Pneumatic Actuators)
-
Sleeves of Various Depths and Gauge Thicknesses (restriction apply)
-
No Sleeves (restriction apply)
-
Round or Oval Transitions
-
Short-Width (<8”) and/or Short-Height (<6”) Transitions
DATA SHEETS
-
Installation Instruction
-
Supplementry Information
NOTES
-
Damper frames are provided approximately ¼ undersized. The addition of a sleeve will increase the size of the assembly.
-
Damper with smoke detector must have a minimum sleeve of 19” (10.5” on the actuator side and 3” on the non-actuator side).
-
Dampers for horizontal installation can only be mounted in a fire barrier constructed of masonry/concrete materials.