LA2
Combination Fire / Smoke Damper
Class II • Airfoil Blade • 3 Hour • 250°F or 350°F • Galvanized Steel • UL Classified Damper
STANDARD CONSTRUCTION
Frame
Frame Type
Blade
Blade Type
Axle materials
Axle Bearings
Linkage
Blade Seal
Jamb Seal
Closure Device
Closure Temp.
: 16-GA galvanized steel
: 5½" X ⅞" Galvanized steel Hat Channel
: 20-GA Double skin ( equivalent to 14-GA )
: Airfoil type
: Plated Solid Steel stub
: Oil impregnated bronze
: Plated steel angle & crank plates with stainless steel
pivots; In-jamb type
: Silicone
: Stainless steel
: Electric heat responsive device
: 165º F (73ºC)
OPTIONS
-
Exact Size (no undercut)
-
Actuators - 120V, 24V, 230V or Pneumatic
-
Right Hand and/or Internal Actuator Mounting Locations (Restrictions Apply) Integral Dual Position Indication (IDPI) Switches
-
Sensotherm Re-Openable Heat Response Device (ESOT) for Electric Actuator
-
Sensotherm Re-Openable Heat Response Device (PSOT) for Pneumatic Actuator
-
Model SM-501 Flow-Rated Smoke Detector (10” Minimum Damper Height)
-
Model 2151 No-Flow Smoke Detector (12” Minimum Damper Height)
-
Momentary Test Switch Remote Test Box
-
Transformers
-
Tab-Lock Retaining Angles
-
Stainless Steel Bearings
-
Stainless Steel Axles
-
Security Bars
-
Copper Tubing (for Pneumatic Actuators)
-
Sleeves of Various Depths and Gauge Thicknesses (restriction apply)
-
No Sleeves (restriction apply) Round or Oval Transitions
-
Short-Width (<8”) and/or Short-Height (<6”) Transitions
DATA SHEETS
-
Installation Instruction
-
Supplementry Information
NOTES
-
Damper frames are provided approximately W¼” undersized. The addition of a sleeve will increase the size of the assembly.
-
Damper >= 12” in height with factory mounted SM-501 smoke detectors require a minimum 19” deep sleeve (10.5” on the actuator side); detectors will be mounted on the side of the damper opposite actuator.
-
Damper < 12” in height with factory mounted SM-501 smoke detectors require a minimum 20 deep sleeve (11.5” on the actuator side); detectors will be mounted on the bottom or top of damper.
-
Smoke Detectors can be ordered for field mounting with standard 18” deep sleeve.
-
Dampers for horizontal installation can only be mounted in a fire barrier constructed of masonry/concrete materials.